Solenoid Control Valve

Product Advantages

  • Fast Acting Solenoid Control
  • Reliable, Drip-Tight Shut-Off
  • Simple Design, Proven Reliable
  • Optional Check Feature
  • Easy Installation and Maintenance

The Cla-Val Model 136-01 Solenoid Control Valve is an on-off control valve that either opens or closes upon receiving an electrical signal to the solenoid pilot control. This valve consists of a Hytrol main valve and a three-way solenoid valve that alternately applies pressure to or relieves pressure from the diaphragm chamber of the main valve. It is furnished either normally open (de-energized solenoid to open) or normally closed (energized solenoid to open). If the check feature option is added and a pressure reversal occurs, the downstream pressure is admitted into the main valve cover chamber and the valve closes to prevent return flow.

Schematic Diagram

Item Description
1.  100-01 Hytrol Main Valve
2.  CS3 Solenoid Control

Optional Features

Item Description
A.  X46A Flow Clean Strainer
B.  CK2 Isolation Valve
C.  CNA Closing Speed Control
D.  Check Valves with Isolation Valve
P.  X141 Pressure Gauge
S.  CNA Needle Valve (Opening)
V.  X101 Valve Position Indicator
Y.  X43 “Y” Strainer


Typical Applications

Industrial uses for the solenoid control valve are many and include accurate control of process water for batching, mixing, washing, blending or other on-off type uses.

Liquid level control can be provided by using a float switch or electrode probe which sends an electrical signal to open or close the valve as needed.


Model 136-01 (Uses Hytrol Main Valve Model 100-01)

Pressure Ratings (Recommended Maximum Pressure – psi)

Materials

Model 136-01 Dimensions (inches)


Model 136-01 Metric Dimensions (Uses 100-01 Hytrol Main Valve)

Model 136-01 Dimensions (mm)

* Non Guided Stem Auxillary Hytrol Controls



Pilot System Specifications

Temperature Range
Water: to 180°F/82°C

Fluids
Air, water, light oils

Solenoid Control
Body:
Brass ASTM B283

Rubber Parts:
Buna-N® Rubber Synthetic Rubber

Enclosure:
NEMA Type 1,2,3,3S,4,4X general purpose watertight*
NEMA Type 6,6P,7,9 Watertight Explosion Proof available.

Voltages:
110, 220 -50Hz AC
24, 120, 240, 480 – 60Hz AC
6, 12, 24, 120, 240 – DC
Others available at additional cost

Max. operating pressure differential:
200 psi*

Coil:
Insulation molded Class F
Watts AC 6
AC Volt Amps Inrush 30
AC Volt Amps Holding 16
Watts DC 10.6
Manual operator available at additional
cost.

* Supplied unless otherwise specified
Note: Flowing Pressure Differential: 5 psi minimum

Valve Options

X141 Pressure
Gauge

X101AR Valve
Position Indicator
with Air Release

X101
Valve Position
Indicator

X144 e-FlowMeter

X43H
Strainer

X43H
Strainer

Stainless
Steel Pilot