Float Valve
Product Advantages
- Accurate and Repeatable Level Control
- On-Off or Non-Modulating Action
- Fully Adjustable High and Low Level Settings
- Simple Design, Proven Reliable
- Easy Installation and Maintenance
The Cla-Val Model 124-01 Float Valve is a non modulating valve that accurately controls the liquid level in tanks. This valve is designed to open fully when the liquid level reaches a pre-set low point and close drip tight when the level reaches a preset high point. This is a hydraulically operated, diaphragm valve with the pilot control and float mechanism mounted on the cover of the main valve. The float positions the pilot control to close the valve when the float contacts the upper stop. The high and low liquid levels are adjusted by positioning the stop collars on the float rod. The difference between high and low levels can be adjusted to as little as 1″ (25 mm), or to as much as 18″ (450 mm). Level settings can be as much as eleven and one half feet below the valve. The float mechanism may be located remotely from the main valve. See the technical data sheet on Model CF1-C1 Float Control for additional information.
Schematic Diagram
Item Description
1. 100-01 Hytrol Main Valve
2. CF1-C1 Float Control
Optional Features
Item Description
A. X46A Flow Clean Strainer
B. CK2 Isolation Valve
C. CV Flow Control (Closing)
F . Independent Operating Pressure
P. X141 Pressure Gauge
S. CV Speed Control (Opening)
V. X101 Valve Position Indicator
Y. X43 “Y” Strainer
Typical Applications
The Model 124-01 Float Valve is commonly mounted above the high water level in a tank. Globe pattern valves are supplied standard with the float control mounted on the cover as illustrated, with a horizontal discharge. Angle pattern valves are configured to discharge downward.
Notes:
- We recommend protecting tubing and valve from freezing temperatures.
- Must be inspected periodically.
Typical Applications
A stilling well (8″ / 300mm minimum diameter) must be provided around the float. When the valve is mounted on top of the tank roof, a 2″ (50mm) clearance hole should be provided for side movement of the float rod where the rod goes through the top of the tank.
A clear independent source of air or water may be used to operate the valve (option F). The pressure from this independent source must at all times be equal to or greater than pressure at the valve inlet.If minimum flowing line pressure is less than 10 psi, consult factory.
If the float control is remotely mounted from the main valve, the control may be installed at any elevation above the valve, provided the flowing line pressure in psi is greater than the vertical distance in feet between the valve and the float control. See the technical data sheet on Model CF1-C1 for additional information.
Model 124-01 (Uses 100-01 Hytrol Main Valve)
Pressure Ratings (Recommended Maximum Pressure – psi)
Materials
Model 124-01 Dimensions (inches)
Model 124-01 Metric Dimensions (Uses 100-01 Hytrol Main Valve)
Model 100-01 Full
Port Hytrol Main Valve
CF1-C1 Stainless Steel Float
Float Control Overview
The Cla-Val Model CF1-C1 Float Control is a float-actuated, multi-port pilot control which provides non-modulating, two-position, on-off operation. It is used primarily to operate remotely located Cla-Val valves requiring three-way or four-way pilot valve operation. Designed for used in open tanks, this control operates on a minimum level change of approximately one inch.
Model 124-01 Dimensions (mm)
Pilot System Dimensions
124-01Float Valve (Globe)
124-01Float Valve (Angle)
Notes:
- *Z (Max.) is with standard float rod.
- We recommend providing adequate space around valve for maintenance work
- Dimensions cover Threaded, Flanged and Grooved connections.
Pilot System Dimensions
Pressure Rating
300 psi Max.
Temperature Rating
Water: to 180°F (82°C) Maximum
Materials
In contact with operating fluid:
Nylon-reinforced Delrin,Stainless Steel,
Monel, with Buna-N® seals
Float linkage and float rod: Brass and PVC
Base plate: 316 Stainless Steel
Float: 304 Stainless Steel
Float
53/8″ (180mm) diameter.
Float Rod
Standard: Two 12″ (300mm) sections PVC rod,
6″ (150 mm) & smaller
12″ (300mm) extension increments at additional cost.
Larger counterweight required if float rod length exceeds 5′ (1524mm).
Optional: 24″ (600mm) stainless steel rod, with
24″ (600mm) extension increments at additional cost.
Larger counterweight required if float rod lengthexceeds 2′ (600mm).
If maximum temperature exceeds 160°F (71°C) specify
stainless steel float rod.
Adjustment Range
Level Differential:
1″ min. to 18″ max.(25 – 450mm) with PVC rod.
1″ min to 40″ max. (25 – 1016mm) with stainless steel rod.
Operating Fluids
Clean liquids or gases compatible with specified materials.
When Ordering, Please Specify
- Catalog No. 124-01
- Valve Size
- Pattern – Globe or Angle
- Pressure Class
- Threaded or Flanged
- Float Rod Material and Length
- Float Ball Material
- Desired Options
- When Vertically Installed