81-02 Check Valve
Product Advantages
- Simple Proven Design
- No-Slam Operation
- Drip-Tight Shut-Off
- Dual Speed Control
- No Packing Glands or Stuffing Boxes
- Available in a Variety of Materials
The Cla-Val Model 81-02 Check Valve is a hydraulicallyoperated No-Slam Check Valve with dual speed controls. This valve opens when the pressure at the inlet exceeds the discharge pressure. A gradual rate of opening prevents sudden opening surges. When a pressure reversal occurs, the higher downstream pressure is applied to the cover chamber through the control tube lines, and the valve closes drip tight.
This valve is ideally suited for use where a positive shutoff is required. The rubber disc assures tight sealing even if the fluid contains grit or other smallsize particles. The simple packless design insures reliable operation and freedom from leaks.
Note: The effectiveness of this valve is related to pipeline velocity. We recommend a maximum flow based on pipeline velocity of 6 feet per second. If pipeline velocities exceed 6 feet per second, consideration should be given to adding a Cla-Val Model 50-01 Pressure Relief Valve or a Cla-Val Model 52 Series Surge Control Valve to the system.
Schematic Diagram
Item Description
1. 100-01 Hytrol Reverse Flow Main Valve
2. CGAAngle Valve (Closing)
3. CNA Needle Valve (Opening)
4. CSC Swing Check Valve
Optional Features
Item Description
P. X141 Pressure Gauge
V. X101 Valve Position Indicator
Typical Applications
Deep Well Pump
This valve should be an integral part of any well designed pumping system. It is used to prevent damaging and sometimes expensive flow reversal.
Booster Pump
Install on the discharge of booster pumps to prevent return flow into tank when pump is off. Relief valve as shown is good practice to minimize surges when pump stops.
Model 81-02 (Uses 100-01 Hytrol Reverse Flow Main Valve)
Pressure Ratings (Recommended Maximum Pressure – psi)
Materials
Model 81-02 Dimensions (inches)
Model 81-02 Metric Dimensions (Uses 100-01 Hytrol Reverse Flow Main Valve)
Model 100-01 FullPort Hytrol Main Valve
Model 81-02 Dimensions (mm)
Flowrates shown are for a velocity of 6 fps (1.8 m/s).
Velocities can be increased to 10 fps (3.05 m/s) if required, and the installation of a surge valve in the system is recommended in velocities above 6 ft/sec. (1.8 m/sec)
Pilot System Specifications
Temperature Rating
Water: to 180°F/82°C Max.
Speed Controls
Opening and closing speed controls are
standard on the 81-02 Model.
* Note: Advise factory when ordering if valve will
not be installed with the main valve stem in a
vertical position.
Materials
Standard Pilot System Materials
Fittings: Brass
Tubing: Copper
Optional Pilot System Materials
Pilot Systems are available with
optional stainless steel or Monel
materials
Valve Options
When Ordering,
Please Specify
1. Catalog No. 81-01
2. Valve Size
3. Pattern – Globe or Angle
4. Pressure Class
5. Threaded or Flanged
6. Desired Options
7. When Vertically Installed